honda eu2200i overload indicator is red and everything shut off, engine still running though. how do i fix this?

— asked by Chloe

The overload protector tripped because you exceeded 2.2 kVA or have a short circuit in a connected appliance.

  • Disconnect all appliances from the generator.
  • Locate the AC circuit protector button on the control panel. Push it to reset it to ON.

If that didn't work, and the overload indicator is blinking continuously, that indicates an inverter unit failure. Stop the engine and contact a Honda servicing dealer.

Before reconnecting power: Verify the total wattage of all appliances you're plugging in does not exceed the generator's capacity. Faulty appliance cords can also cause this.

0

Different problem with the same product?

Ask about the Honda EU2200i Portable Inverter Generator →